Input Voltage
|
115 or 230VAC, 48…410Hz +/-2 are standard
Other inputs available, please consult factory
|
Input Protection
|
Termal fuse, Inrush current limiting, Reverse polarity protection
|
Isolation
|
2250 VDC input to chassis / 2250 VDC input to output / 2250 VDC output to chassis
|
Output Voltage
|
115VAC / 60Hz / 34.7A or 115VAC / 400Hz / 34.7A or
230VAC 50Hz / 17A continuous with grounded neutral
Isolated ?oating output optional (Consult factory for other voltages and frequencies)
|
Wave Form
|
Sinusoidal
|
Total Harmonic Distortion
|
Less than 5% at full load
|
Efciency
|
Min 8 at full load
|
Line Regulation
|
Maximum 0.5%
|
Load Regulation
|
Maximum +/-6% from 1 load to full load
|
Output Protection
|
Current limiting with short circuit protection, thermal shutdown with automatic recovery in case of continuous overload or insufcient air?ow
|
EMI
|
Meets EN 55022 Class A.
Custom fltering is available as an option
|
Load Crest Factor
|
Maximum 3.0 at 9 load
|
Operating Temperature Range
|
0o C to +50o C
Extended range available (Consult factory)
|
Humidity
|
5 - 95% non-condensing
|
Temperature Drif
|
0.05% per o C over operating temperature range
|
Dimensions
|
6U package for 115Vac output:
6U (10.5”) x 19” x 19”
265 x 482.6 x 482.6 mm
4U package for 230Vac output:
4U (6.97”) x 19” x 19”
177 x 482.6 x 482.6 mm
|
Connections
|
Input: Compression-type terminal
Output: Terminal block
|
Weight
|
24kg (53lb) max for 115 Vac output
16 kg (35 lb) max for 230 Vac output
|
Safety
|
Designed to meet C22.2 No. 107.1 - 01, UL 458 and EN60950
|
Options
|
Output Fail Alarm (Form C)
Remote Inhibit: By connecting DC voltage (as specifed) to the inhibit terminals
|